SPD Tech Circuit Protection Devices & Solutions
中文

Lightning Protection for Photovoltaic Systems

10 min
PVDCInverters

PV is among the most strike-prone installations — module frames, rails, backplanes and DC insulation are all failure points; protect with DC-side SPD (with DC fuses) plus signal-side TVS/ESD.

PV systems suffer lightning damage at rates well above comparable buildings. The reason is not mysterious: a PV array is a large-area, elevated, and directly exposed metal structure sitting in the interception zone.

1. Failure morphologies

Morphology Typical appearance Principal cause
Module burn-out Scorched frames, shattered glass, burnt backplane Direct strike, current discharging through module frames or backplane
DC arcing Burnt DC connectors, tracking-type damage No overvoltage protection on the DC side; strike current heating at terminations
Inverter failure Rupture, insulation faults reported Direct strike coupling or surge ingress into the DC side
Insulation degradation Low insulation resistance, MPPT faults Moisture plus carbonisation following DC arcing

Key observation: the majority of lightning damage in PV systems occurs at connectors and cables, not in the modules themselves. Current takes the path of least impedance, and while the module interior is blocked by semiconductor layers, connector copper is pure metal.

2. Four positions that must be addressed

1. Module frame interception and equipotential bonding

The module frame is exposed metal, and it needs two things:

  • Interception: modules projecting beyond the roof's interception zone need their own down-conductor bonded back to the roof air-termination system
  • Bonding: all module frames, mounting rails, and roof metalwork connected into an equipotential body

Neither alone is sufficient. Bonding without interception means the strike current still flows through the frames — it simply burns the connectors instead of the modules. Interception without bonding leaves the current to find an uncontrolled path through the array, and that is when you get "only some modules destroyed".

2. DC-side SPDs

This is the most frequently omitted and the most critical element of PV protection.

An AC-side SPD does not protect the DC side, because: - The DC side has no neutral reference, so surges superimpose as common-mode voltage across the array - DC voltage is pulsating (pulsating DC, single-polarity grounding systems), so the operating voltage window is wider than on AC - A direct strike current introduced through the array flows straight into the DC cabling

DC-side SPD requirements differ from AC:

Item DC-side requirement
Uc Must cover the maximum open-circuit voltage (Voc), including the low-temperature rise (Voc increases by roughly 5%–10% at low temperature)
Poles Single pole (positive-to-earth, negative-to-earth) or two-pole
Current capacity Must account for how the strike current divides and concentrates within the array
Fusing A DC-specific fuse is mandatory — a DC arc does not self-extinguish
Position Immediately at the inverter DC input (at the combiner)

Never omit the DC fuse

When a DC-side SPD fails short, the arc does not extinguish at a current zero as on AC; it can sustain until the equipment burns down. A DC-specific fuse (gPV class) providing fast disconnection is essential. On AC this can be substituted with an ordinary fuse; on DC it cannot.

3. Inverter and grid interface

The inverter AC output should have a Type 2 SPD, and it must be within one metre of the inverter AC output.

The inverter carries the densest and most expensive electronics in the system, so protecting it deserves the highest priority. Note also that if the inverter connects to a grid that is itself exposed (overhead distribution), the grid connection point needs protection against induced lightning and grid-side switching surges.

4. Mounting structure and earthing

The connection between the PV mounting rails and the roof (embedded plates or clamps) is routinely underestimated. It is the mandatory path for current from the array to the down-conductor.

  • Connections must be reliable (welded or bolted with anti-loosening measures)
  • Rail-to-PE conductor cross-section must meet requirements
  • Roof waterproofing at penetrations: the down-conductor, SPD cables, and combiner all penetrate the roof. After a strike, it is often the roof that leaks first, not the equipment that fails. Inspect this at commissioning.

3. Why rooftop PV is different

① Elevation increases the probability of being struck. Prominent metal structures are struck more readily. Statistically, rooftop PV is significantly more strike-prone than a flat roof of the same area.

② Current distribution within the array is complex. How current divides between module frames depends on the relative connection impedances. Without equipotential bonding, current concentrates on the lowest-impedance path — a particular frame or rail — and destroys that section locally. This is exactly why "only part of the array is damaged".

Equipotential bonding in PV is therefore not optional, in the way it is in some general building applications.

Position Measure
Module frames Dedicated down-conductor where outside the interception zone + equipotential bonding across the array
DC side (combiner / inverter input) DC SPD with DC-specific fuse, immediately at the inverter
Inverter AC output Type 2 SPD within 1 m of the inverter
Grid connection Type 2 SPD where the connection point is on the grid side
Roof penetrations Waterproofing detail at every penetration

5. Additional commissioning checks

Beyond standard SPD acceptance, PV projects should add:

  • [ ] Continuity test record for module frame equipotential bonding
  • [ ] Dedicated down-conductors for modules projecting beyond the interception zone
  • [ ] DC SPD fitted with a DC-specific fuse, correctly coordinated with the SPD
  • [ ] DC SPD Uc covers the maximum Voc at low temperature, including the correction factor
  • [ ] Waterproofing intact at all roof penetrations (down-conductors, SPD cables, combiners)
  • [ ] Mounting connections torqued with anti-loosening measures
  • [ ] Inverter AC-side SPD within 1 m

Extension

PV is the canonical example of the "DC overvoltage" problem. The same issues appear in energy storage systems with DC busbars and battery racks: → Energy storage and DC bus protection