SPD Tech Circuit Protection Devices & Solutions
中文

SPD — Typical Specifications

· 6 min
SPDSurgeIEC 61643Type 1/2/3Specifications

Mainstream commercial specifications, package forms and selection reference for SPD.

Type 1 entrance

Type 1 entrance

Withstands 10/350 µs Iimp 15–150 kA for building entrance / LV side of transformers; paired with T2/T3.

02

Type 2 distribution

In 5–100 kA (8/20 µs) for sub-distribution; modular plug-in, with remote signaling.

03

Type 3 equipment

In 5–20 kA for sensitive equipment; often direct-insert in UL, no §45 In test.

04

Signal / network

Cat.5e/6 and coax types, designed for port impedance and loss, < 1 pF.

05

PV / ESS DC

Uc 1000/1500 V DC, handles DC surge current for PV strings and ESS inverters.

06

Modular plug-in + remote signal

Fault-indication window and remote contact for central inspection.

Mainstream SPDs are offered per IEC 61643-11 as Type 1 / 1+2 / 2 / 3, with rated discharge current In from 5 kA to 200 kA (8/20 µs); Un spans single-phase 230 V to three-phase 690 V and below; Up ranges from a few hundred volts to ~1.5 kV by voltage class. Modular plug-in units (with remote signaling and fault windows) dominate distribution; signal/network types are specified separately for Cat.5e/6 and coax.

Dimension Typical range Note
Class Type 1 / 1+2 / 2 / 3 entrance / distribution / equipment
In nominal discharge 5–200 kA (8/20) by lightning exposure
Uc max continuous 275–750 V (AC) ≥ 1.1× line voltage
Up protection level 0.6–1.5 kV must be < equipment Uw
Form modular plug-in / integral / signal distribution prefers plug-in w/ signaling

Mainstream SPDs are offered per IEC 61643-11 as Type 1 / 1+2 / 2 / 3, with rated discharge current In from 5 kA to 200 kA (8/20 µs); Un spans single-phase 230 V to three-phase 690 V and below; Up ranges from a few hundred volts to ~1.5 kV by voltage class. Modular plug-in units (with remote signaling and fault windows) dominate distribution; signal/network types are specified separately for Cat.5e/6 and coax.

Dimension Typical range Note
Class Type 1 / 1+2 / 2 / 3 entrance / distribution / equipment
In nominal discharge 5–200 kA (8/20) by lightning exposure
Uc max continuous 275–750 V (AC) ≥ 1.1× line voltage
Up protection level 0.6–1.5 kV must be < equipment Uw
Form modular plug-in / integral / signal distribution prefers plug-in w/ signaling