SPD Tech Circuit Protection Devices & Solutions
中文

Standards Landscape — Four Families and Test Waveforms

· 11 min
standardswaveformsIEC 61643UL 1449GB/T 18802

Distinguish SPD product standards (IEC 61643 / UL 1449 / GB/T 18802) from equipment immunity standards (IEC 61000-4-5), and build a "system + waveform" analysis framework.

1. Two kinds of standards, first

The most common confusion: SPD product standards and equipment immunity standards are not the same thing.

Type Examples What it governs
SPD product standard IEC 61643, UL 1449, GB/T 18802 The SPD's own performance, classification, test methods and safety
Equipment immunity standard IEC 61000-4-5, GB/T 17626.5 How much surge the protected equipment must withstand (surge immunity)

Why they get mixed up

Both talk about "surge" and both use the 1.2/50 µs – 8/20 µs combination wave, but with opposite intent: product standards test whether the SPD can divert; immunity standards test whether the equipment survives. When selecting an SPD, its Up must leave enough margin below the equipment's immunity level (withstand voltage Uw).

2. Four / five families at a glance

Family Nature Region Key documents Relationship
IEC 61643 International (product) Most of the world -01 general; -11 AC power; -12 application; -21/-22 telecom; -31/-32 PV The parent of GB/T 18802 (MOD)
UL 1449 North-American safety cert. US / Canada Edition 5 (2022, current) Self-contained; not directly interchangeable with Chinese standards
GB/T 18802 Chinese national (MOD IEC) Mainland China .11-2020 power; .12-2014 application; .21-2016 telecom MOD of IEC 61643, paired with CQC certification
IEC 61000-4-5 / GB/T 17626.5 Equipment immunity Global / China Surge immunity base standard Sets the equipment withstand level

3. Test waveforms — the start of every parameter discussion

The "fatness" of a waveform decides its energy. At the same peak current, a long-tail wave carries far more energy than a short one.

Waveform Shape Typical use
1.2/50 µs Open-circuit voltage surge Equipment immunity, SPD open-circuit voltage test
8/20 µs Lightning current (short tail) Type 2 In, Imax tests
10/350 µs Lightning current (long tail) Type 1 Iimp (direct-lightning charge)
10/1000 µs Lightning current (long tail) Some MOV / varistor energy tests
1.2/50 µs + 8/20 µs combination Combination wave Equipment immunity, UL 1449 VPR test

Waveform before numbers

The same SPD may show In = 20 kA at 8/20 µs but only ~4 kA at 10/1000 µs — same peak, several times the energy. Comparing like-named parameters across systems or waveforms is meaningless; unify the system first, then the waveform.

4. Cross-system comparison discipline

  1. Identify the standard family (IEC / UL / GB) the parameter belongs to;
  2. Then confirm the test waveform of each current / voltage parameter;
  3. Only then compare values, checking clause numbers and edition years;
  4. For certification conclusions, UL 1449 test results cannot stand in for a GB/T 18802 / IEC 61643 certificate, and vice versa.

5. Next


1. Two kinds of standards, first

The most common confusion: SPD product standards and equipment immunity standards are not the same thing.

Type Examples What it governs
SPD product standard IEC 61643, UL 1449, GB/T 18802 The SPD's own performance, classification, test methods and safety
Equipment immunity standard IEC 61000-4-5, GB/T 17626.5 How much surge the protected equipment must withstand (surge immunity)

Why they get mixed up

Both talk about "surge" and both use the 1.2/50 µs – 8/20 µs combination wave, but with opposite intent: product standards test whether the SPD can divert; immunity standards test whether the equipment survives. When selecting an SPD, its Up must leave enough margin below the equipment's immunity level (withstand voltage Uw).

2. Four / five families at a glance

Family Nature Region Key documents Relationship
IEC 61643 International (product) Most of the world -01 general; -11 AC power; -12 application; -21/-22 telecom; -31/-32 PV The parent of GB/T 18802 (MOD)
UL 1449 North-American safety cert. US / Canada Edition 5 (2022, current) Self-contained; not directly interchangeable with Chinese standards
GB/T 18802 Chinese national (MOD IEC) Mainland China .11-2020 power; .12-2014 application; .21-2016 telecom MOD of IEC 61643, paired with CQC certification
IEC 61000-4-5 / GB/T 17626.5 Equipment immunity Global / China Surge immunity base standard Sets the equipment withstand level

3. Test waveforms — the start of every parameter discussion

The "fatness" of a waveform decides its energy. At the same peak current, a long-tail wave carries far more energy than a short one.

Waveform Shape Typical use
1.2/50 µs Open-circuit voltage surge Equipment immunity, SPD open-circuit voltage test
8/20 µs Lightning current (short tail) Type 2 In, Imax tests
10/350 µs Lightning current (long tail) Type 1 Iimp (direct-lightning charge)
10/1000 µs Lightning current (long tail) Some MOV / varistor energy tests
1.2/50 µs + 8/20 µs combination Combination wave Equipment immunity, UL 1449 VPR test

Waveform before numbers

The same SPD may show In = 20 kA at 8/20 µs but only ~4 kA at 10/1000 µs — same peak, several times the energy. Comparing like-named parameters across systems or waveforms is meaningless; unify the system first, then the waveform.

4. Cross-system comparison discipline

  1. Identify the standard family (IEC / UL / GB) the parameter belongs to;
  2. Then confirm the test waveform of each current / voltage parameter;
  3. Only then compare values, checking clause numbers and edition years;
  4. For certification conclusions, UL 1449 test results cannot stand in for a GB/T 18802 / IEC 61643 certificate, and vice versa.

5. Next