Type 3 Cord-Connected SPD — UL 1449 Test Deep-Dive
Item-by-item breakdown of Cord-Connected / Direct Plug-in Type 3 SPDs (surge-protected power strips / extension cords): spec definition, test criteria and a ready-to-use spec sheet under UL 1449 5th Edition.
Product scope
Cord-Connected / Direct Plug-in Type 3 SPDs: surge-protected power strips & extension cords.
To textMCOV selection
MCOV must be ≥ 250 VAC; a multi-outlet strip must never exceed MCOV under load.
To textIn & VPR
Type 3 skips the In sequence; VPR is graded on the 6 kV / 3 kA combination wave.
To textCriteria → spec sheet
Each acceptance criterion maps directly to a spec-sheet (Spec) field.
To text1. What this article solves
A "surge-protected extension cord / power strip" is, in the UL system, a Type 3 SPD in the Cord-Connected / Direct Plug-in form — the product carries its own cord (cord-connected) or plug (direct plug-in) and plugs into the utilization side, rather than being hard-wired at the panel.
Its UL test path and acceptance criteria are entirely different from Type 1/2, and are not directly equivalent to IEC 61643-11 (residential). This article works from UL 1449 5th Edition (2021-01-08, 152 pages) against the printed page numbers, tying "spec definition → test → acceptance" together, and ends with a spec-sheet skeleton you can ship.
Not interchangeable with IEC
A surge strip exported to North America must be evaluated under UL 1449 on its own. An IEC 61643-11 "residential" result cannot stand as a UL Type 3 basis, and vice versa. Waveforms, criteria and limits are self-contained.
2. Product scope (P1–P4)
- Cord-Connected SPD: carries its own cord and plug, plugged at the utilization end (power strip, surge extension cord).
- Direct Plug-in SPD: shaped as a receptacle/plug, plugged straight into a wall receptacle to protect downstream loads.
Common traits:
| Attribute | Note |
|---|---|
| Class | Type 3 (point of utilization) |
| Location | ≥ 10 m (30 ft) of conductor from the service panel (excluding its own leads) |
| Voltage | 120/240 VAC systems |
| Typical loads | consumer electronics, office, light-duty tools |
| SCCR required | Direct plug-in / cord-connected do not require an SCCR rating (Type 3 skips the §45 short-circuit test) |
Because it sits far out at the utilization point, an upstream SPD (Type 1/2 at the panel) absorbs most of the lightning energy; the Type 3 only handles the residual voltage. So its acceptance focus is residual voltage limitation (VPR / limiting voltage), not fault-current handling.
3. Key parameters & terms (P5–P8)
Four core quantities: MCOV, Un, VPR, MLV (§3.20 / §3.21 / §3.27 / §3.54 · p.12–15):
- MCOV (Max. Continuous Operating Voltage, §3.20): the highest rms sinusoidal voltage that can be applied continuously to the SPD's protection mode. For a 120 V system use 150 V (≈1.25× margin); step up for UPS / generator scenarios.
- Un (Normal working voltage, §3.27): the manufacturer-designated AC rated voltage, usually the system phase voltage (120/208/240/277/480/600 V). Outlet class per UL 498 is marked 125 V / 15 A.
- VPR (Voltage Protection Rating, §3.54): the average MLV measured on the 6 kV / 3 kA combination wave, then rounded up to the next step in Table 84.1's 17 preferred values (330–6000 V) — it is not a free-form number. Typical 3-mode: L-N 330 / L-G 330 / N-G 500 V.
- MLV (Measured Limiting Voltage, §3.21): the actual maximum voltage seen at leads / terminals / contacts after applying the specified waveforms; it is the measured basis for VPR and is not printed on the nameplate.
One line to remember: MCOV decides "can it stay connected long-term here", VPR decides "how much gets through during a surge"; MLV is what the lab measures, VPR is what you pick from the preferred-value table.
4. Type 3 test items & criteria (P9–P14)
Per UL 1449 5th Edition (clause + printed page of that edition):
| Test | Clause | Page | Pass criterion |
|---|---|---|---|
| Surge / combination | §41 (§41.6 VPR baseline, §41.8 duty cycle, §41.9 retest) | p.61–62, 81–83 | no breakdown / persistent short throughout; VPR drift ≤ 10% |
| Leakage current | §38.1 (cord / direct-plug Type 3 only) | p.62 | ≤ 0.5 mA; may relax to 3.5 mA with the §85.9 WARNING |
| Dielectric | §39.1.1–39.2.2 | p.66–67 | primary: 1000 V + 2× rated; isolated secondary per Table 39.1 (0–1000 V → 3V, min 500 V) |
| Temperature rise | §40.1–40.2 (mandatory for Two-Port) | p.68–69 | absolute temp caps (not a rise): MOV body 85 ℃ / outlet contact 55 ℃ / insulated conductor 60 ℃ / junction box 90 ℃ (19 items) |
| Current class | §45.3 / §45.4 / §45.2 | p.85–86 | cord / direct-plug Type 3 skips §45 and carries no SCCR (§84.1 forces it only on "permanent-wired, non-outlet" Type 3) |
| Grounding continuity | §49 | p.92–95 | impedance ≤ 0.1 Ω |
The "pass line" for a cord / direct-plug Type 3 strip = combination wave (§41) + leakage (§38) + dielectric (§39) + temperature rise (§40) + grounding continuity (§49) all met, with no §45 short-circuit test and no SCCR rating.
5. Shipping it: spec-sheet skeleton (P15–P17)
Map the clauses into a spec sheet you can hand to customers / factories:
| Spec field | Typical value (120 V single-phase) | Clause · page |
|---|---|---|
| Product class | Cord-Connected / Direct Plug-in Type 3 SPD | §1.17 / §1.18 · p.7–8 |
| Working voltage Un | 120 V~ / 60 Hz | §3.27 |
| MCOV | 150 V~ (≥ 1.1 × Un) | §3.20 |
| VPR | L-N 330 / L-G 330 / N-G 500 V (must sit within Table 84.1's 17 steps) | §3.54 / §84.1 · p.129 |
| In | 3 kA (may be left unmarked); Type 3 runs no standalone In test | §3.24 / §41.7 · p.61 |
| Leakage current | ≤ 0.5 mA (3.5 mA with WARNING) | §38.1 · p.62 |
| Outlets / current | Two-Port must mark load current, e.g. 6 × 15 A | §3.28 / §3.52 · §84.1 |
| Short / SCCR | cord / direct-plug carries no SCCR | §84.1 · p.128 |
| Temp cap | MOV body 85 ℃ / contact 55 ℃ / insulated conductor 60 ℃ | Table 40.1 · p.68–69 |
| 10 m warning | must mark "do not install if < 10 m (30 ft) conductor", unless In (≥3 kA) was run per §41.8.1 | §85.4 |
For spec authors
Ship at minimum: Un / MCOV / VPR (per protection mode) / leakage / outlet count & current / short-circuit handling (cord·direct-plug is SCCR-exempt) / temp caps. Write "combination wave 6 kV / 3 kA" into the spec so downstream users don't mis-apply the old SVR number; keep a marking checklist (§85.1 a–i) signed off by both structure and quality before certification — far cheaper than rework afterwards.
6. Common misconceptions (P18)
- Type 3 ≠ "no tests at all": it skips §45 short-circuit and standalone In, but still runs combination wave (§41), leakage (§38), dielectric (§39), temperature rise (§40) and grounding continuity (§49).
- Higher VPR than old SVR is not worse: different test current (3 kA vs 0.5 kA), not comparable side-by-side.
- 0.5 mA is not a human-perception threshold: it is the standard's limit for cord / direct-plug Type 3 (≈11 nF total capacitance at 120 V / 60 Hz); human 60 Hz let-go current is in the milliamp range (typically 5–10 mA).
- Two dielectric formulas must not be mixed: primary 1000 + 2× rated; isolated secondary per Table 39.1 (0–1000 V → 3V, min 500 V).
- A "surge" strip is not lightning-proof: it's a residual-voltage device and requires an upstream SPD to absorb the main energy first.